Lighting calculator: how many downlights and how many lux you need
Work out how many recessed downlights a room needs for the lux level you want, drag them on the ceiling plan and see how the light spreads on a heat map.
Drag each downlight to move it, or use the arrow keys (Shift = big step). Color shows lux: yellow is above the target.
Results
154 lx
Level reached
With 8 downlights of 800 lm, the 20 m² room reaches about 154 lx (target: 150 lx). Uniformity 0.47.
- Downlights needed
- 8
- you have 8 on the plan
- Total power
- 71 W
- 3.6 W per m²
- Uniformity
- 0.47
- minimum 72 lx, maximum 201 lx
Lighting design for your project?
We design the light of each room together with the scenes and the automation, from the plans. Tell us about your project and we will advise you.
Estimate for guidance. The final design is set by measuring the room on site.
Placing downlights by eye often ends in a room with bright spots and dim corners, or with more fixtures than were needed. The calculator above tells you how many recessed downlights a room needs for the lux level you want and also lets you drag them on the ceiling plan to see how the light spreads on a heat map.
How to use the calculator
- Enter the room measurements: width, length and ceiling height.
- Choose the light level with a shortcut (living room, bedroom, kitchen, bathroom, study) or type the lux you want.
- Describe the downlight: the lumens of each one (they are on its data sheet), the beam angle and how many you will fit. Set to N puts in the quantity the calculation asks for.
- Drag the downlights on the plan, or move them with the keyboard arrows. Arrange in a grid spreads them out again.
- Check the results: average lux, downlights needed, power and uniformity. Copy the link to share the plan with whoever installs it.
Lux and lumens: what each one is
Lumens measure the light a fixture emits; lux measure the light that reaches a surface, that is, one lumen spread over one square meter. That is why the same bulb gives lots of lux up close and few far away: what matters for a room is the lux on the work plane (the calculator uses 0.8 m above the floor).
How it is calculated
- Quantity needed (lumen method):
N = lux × m² ÷ (lumens × utilization factor × maintenance factor), rounded up. The utilization factor (60% to start) covers the light lost on walls and ceiling; the maintenance factor (80% to start), dust and the aging of the fixture. - Light spread: each downlight is treated as a point source whose intensity falls with the angle according to the beam you choose; on the work plane, the direct light falls with the square of the height. A uniform diffuse part, the light bouncing off walls and ceiling, is added to that direct light, and the whole is scaled so the average matches the lumen method.
- Uniformity: the minimum divided by the average. A common reference for general lighting is 0.4 or more; below that, the calculator warns that the spread is uneven.
- Power:
downlights × lumens ÷ efficacy, starting at 90 lm/W.
The levels for each room are starting points: guides vary by source. For general lighting, figures of roughly 100 to 300 lux are cited for a living room, 100 to 200 for a bedroom, 200 to 500 for a kitchen (more on the countertop), 200 to 300 for a bathroom and 300 to 500 for a study. Change them to suit how you use the space.
An example
A 5 × 4 m living room (20 m²) with a 150 lux target and 800 lm downlights needs 150 × 20 ÷ (800 × 0.6 × 0.8) = 7.8, that is 8 downlights. They draw about 71 W in total (3.6 W per m²) and leave the room at about 154 lux with a uniformity of 0.47.
More cases with the same 800 lm downlights:
| Room | Target | Downlights | Power |
|---|---|---|---|
| 5 × 4 m living room | 150 lux | 8 | 71 W |
| 4 × 3 m bedroom | 100 lux | 4 | 36 W |
| 4 × 2.5 m kitchen | 300 lux | 8 | 71 W |
| 2.5 × 2 m bathroom | 200 lux | 3 | 27 W |
| 3 × 3 m study | 400 lux | 10 | 89 W |
How the assumptions change the result
For the 5 × 4 m living room at 150 lux:
| Change | Downlights needed |
|---|---|
| 400 lm downlights | 16 |
| 600 lm downlights | 11 |
| 800 lm downlights (start) | 8 |
| 1,200 lm downlights | 6 |
| 1,600 lm downlights | 4 |
| Utilization factor of 40% | 12 |
| Utilization factor of 80% | 6 |
| Maintenance factor of 60% | 11 |
| Maintenance factor of 100% | 7 |
Fewer downlights with more lumens use the same power but spread the light worse. With the same room and 8 downlights, a 30° beam drops the uniformity to 0.32 and a 90° one raises it to 0.55: a wider beam spreads more evenly, a narrow one concentrates the light under each fixture.
What the calculator does not see
It is an indicative estimate for planning. A real lighting design also covers:
- Task and accent light: the countertop, the bathroom mirror, reading or a painting call for directed light on top of the general light.
- Color and light quality: color temperature, color rendering and glare.
- Scenes and dimming: the same fixture does not always have to give the same level.
- Real surfaces: the color of walls and ceiling changes how much light bounces back.
- High or sloped ceilings, beams or services that change where the fixtures fit.
Frequently asked questions
How many lux do I need in a living room?
General-lighting guides cite roughly 100 to 300 lux. The calculator starts at 150; raise it if you read or work in the space.
How many recessed downlights do I need for 20 m²?
It depends on the lumens of each one and the level you want. With 800 lm downlights and 150 lux, about 8; with 1,200 lm downlights, about 6.
Do more lumens mean better lighting?
Not necessarily. What matters is the level that reaches where you need it, an even spread and the ability to dim. A few very powerful fixtures leave dark areas and cause glare.
Want to design the light for your project?
At DomuLab we design the light of each room together with the scenes and the automation, from the plans. Learn about our lighting line and tell us about your project so we can advise you.