Rack UPS calculator: VA, battery and runtime during a blackout
Add up your rack's consumption and work out the VA, battery Wh and runtime you need, or how long the UPS you already have will last.
Drag the point to change the hours, or use the arrow keys. The horizontal line is your UPS battery: where they cross is your runtime.
Results
531 Wh
Your UPS is enough
Your rack draws 153 W (191 W with margin). For 2 h of runtime you need about 531 Wh of battery and 213 VA. Your UPS (1,500 VA, 600 Wh) lasts 2 h 49 min: it is enough.
- Rack load
- 153 W
- 191 W with the growth margin
- Power needed
- 213 VA
- your UPS: 1,500 VA
- Runtime of your UPS
- 2 h 49 min
- with 600 Wh of battery at the current load
Power backup for your rack?
We size the backup for the network and the automation together with the rack, from the plans. Tell us your equipment and we will advise you.
Estimate for guidance. The final design is set by measuring the room on site.
When the power goes out, the first thing worth keeping on is the rack: the router, the switch, the home controller and the storage. The calculator above adds up what your rack draws and tells you how many VA and how many battery Wh you need for the runtime you want, or how long the UPS you already own will last.
How to use the calculator
- Enter the quantity of each type of rack equipment. The power per device is under Power per device: they are starting values, replace them with the ones on your data sheets.
- Pick the runtime you want, by dragging the point on the chart or typing the hours.
- Enter your UPS data (VA and battery Wh) to see how long it lasts and whether it has enough power.
- Review the assumptions (power factor, efficiency, usable discharge and margin): they are in plain view and can be changed.
- Copy the link to share the calculation with whoever installs the backup.
How it is calculated
- Load:
W = Σ quantity × powerof each device. - Power needed:
VA = W × (1 + margin) ÷ power factor. - Battery needed:
Wh = W × (1 + margin) × hours ÷ (efficiency × usable discharge). - Runtime of your UPS:
hours = UPS Wh × usable discharge × efficiency ÷ W.
The starting values are assumptions: power factor 0.9; inverter efficiency 90%; usable battery discharge 80%; growth margin 25%. None is manufacturer data, and each device’s consumption depends on the model and its load.
How much battery for each load
With the starting assumptions:
| Rack load | VA | 1 hour | 2 hours | 4 hours |
|---|---|---|---|---|
| 100 W | 139 VA | 174 Wh | 347 Wh | 694 Wh |
| 150 W | 208 VA | 260 Wh | 521 Wh | 1042 Wh |
| 200 W | 278 VA | 347 Wh | 694 Wh | 1389 Wh |
| 300 W | 417 VA | 521 Wh | 1042 Wh | 2083 Wh |
| 500 W | 694 VA | 868 Wh | 1736 Wh | 3472 Wh |
An example
A rack with one router (15 W), one switch (30 W), one NAS (40 W), one controller (20 W) and four access points of 12 W adds up to 153 W. With the 25% margin, 2 hours takes about 531 Wh of battery and 213 VA. A 1500 VA UPS with 600 Wh of battery would last about 2 h 49 min.
How the assumptions change it
For the same 153 W load and 2 hours:
| Change | Battery needed |
|---|---|
| No growth margin | 425 Wh |
| 25% margin (starting value) | 531 Wh |
| 50% margin | 637 Wh |
| 60% usable discharge | 708 Wh |
| 80% efficiency | 598 Wh |
What else matters
- Real capacity. Batteries lose capacity with age, heat and deep discharges; leave margin instead of sizing to the limit.
- Power and battery. A UPS can have plenty of VA and a short battery: the calculator checks both.
- Draw at full load. A NAS with busy drives or a switch with PoE maxed out draws more than at idle; use the data-sheet value for the demanding case.
- What to back up. Usually the router, the switch, the access points and the controller; big loads such as air conditioning go a different way.
Frequently asked questions
How many VA do I need for a home network rack?
It depends on the load: at 150 W and the starting assumptions, about 208 VA. Work out yours by adding up your equipment.
What is the difference between VA and W?
VA measure apparent power and W real power; the ratio is the power factor. That is why the calculator divides the W by the power factor to get the VA.
How many hours does a UPS last?
As many as its battery gives: Wh × usable discharge × efficiency ÷ the load in W. Enter the Wh from your data sheet and the calculator tells you.